CODE 74 ON CARRIER MODEL 25HNB6
Recently I have taken several calls on code 74 on Carrier 25HNB6 systems. This code basically means the compressor is not operating. This issue can be initiated by several issues associated with non-sufficient voltage to the compressor. The tech exhausted everything he had read about and was thoroughly dissatisfied by information listed in the Carrier service manuals.
The tech checked voltage, the capacitor, contactor, wiring, and fuses. He looked for burned wires swollen capacitors, shortages, frayed wires, grounds in components, pitted contacts on contactor, amp draws, and voltage drop across the contactor. This tech checked the refrigerant and low- and high-pressure controls.
The tech ohmed out the compressor and looked for the proper readings across his start and run windings. He ended up changing the capacitor even though the capacitor had the proper MFD readings. This did not start the compressor and did not remove code 74.
He then called the the tech line and asked for a call from tech support. I took the call. I called the technician and listened to his frustrations. He was ready to condemn the compressor for his customer. He wanted to confirm a bad compressor with tech support before condemning the compressor.
I listed all of his data after listening closely to him and analyzing every step the tech had taken. All his checks were accurate. I even went over several voltage checks with him to verify his work. All were spot on.
I then asked the technician had he tried a hard start or hard start kit? He replied “no”, that he did not think about this as a solution to code 74. I asked him if he had one on his truck. He said he did and would go get it, install it, and give me a return call.
After a few minutes the technician did call me back. The hard start started the compressor and the code 74 went away.
Sometimes, we all need to think outside of the box or norm to try and solve our problems. Obviously, Carrier can’t publish everything to correct code 74 or other codes. We have to rely on our experience and constantly communicating with other like-minded techs to solve some of the troubleshooting issues.
Disclaimer: The technical statements, information and recommendations contained herein are believed to be accurate as of the date hereof, but Mingledorff’s does not make representations or warranties, express or implied, as to its accuracy, its completeness, or the results to be obtained. The information is being provided for informational purposes only and is intended for use by persons having adequate skill and expertise regarding the proper selection, use and application of the products and recommendations and at their own risk and discretion.